Samwha : Protección : EOCR
|
| |
|
| |
|
| |
|
|
 |
EOCR-3M420

|
|
EOCR-FM420
|
|
|
| |
Compact
Design |
| |
3M420:Panel
Mounting Type |
| |
FM420:Panel
Flush Mounting Type |
| |
MCU( Microprocessor Control Unit )&ASIC Based |
| |
Three
Integral Current Transformers |
| |
Over current/Under current/Phase Loss/Phase Reversal/Phase
Unbalace/Locked Rotor |
| |
Digital Ammeter |
| |
Troubleshooting/Trip Cause Memory, Display |
| |
Adjustable
Operating Features by Pulae Rotary switch |
| |
Wide
Current Adjustment Range |
| |
Selectable
Time-Current Characteristics(Inverse/Definite) |
| |
Manual
Instantaneous/Electrical Remote Reset |
| |
Built in 4~20mA Currnt signal Transducer |
| |
Ambient
Insensitive |
| |
Selectable
Fail-safe and Non-fail-safe Operation Modes |
|
|
 |
 |
|
| |
|
Protective Item
|
Trip
Time
|
|
Over-current
|
DEF:0.2~30sec,
INV:1~30
|
|
Undercurrent
|
0.5~30sec(DEF)
|
|
Phase
Unbalance
|
0.1sec
|
|
Phase
Reversal
|
8sec
|
|
Locked
Rotor
|
Lock
|
0.5sec
after dt
|
|
stall
|
1~10sec
|
|
Transducer
|
4~20mA(for
Max current)
|
|
|
|
|
 |
|
| |
|
Model
|
3M420/FM420
|
|
Current Setting Range
|
Over-Current(oc)
|
0.1~800A(over
60A with External CTs)
|
|
Under-Current(uc)
|
0.5~under
OC setting
|
|
Time
Setting
|
Starting
Delay Time(dt)
|
OFF~200sec
|
|
Over-Current
Trip (ot)
|
DEF:0.2~30sec/INV:1~30
|
|
Under-Current
Trip (ut)
|
0.5~30sec(DEF)
|
|
Conrol
Power
|
220
|
85~250VAC/DC,
50/60Hz
|
|
Output
Relay
|
OL
|
2-SPST,
3A/250VAC, Resistive
|
|
Signal
current
|
4~20mA
|
|
Environment
|
Temperature
|
Store
|
-30
~ 80 ¡É
|
|
Operation
|
-30
~ 60 ¡É
|
|
Humidity
|
30~85%RH,
Non-condensation
|
|
Display
|
7-Segment
LEDs
|
3
Phase current, 3 Trip causes, Run time
|
|
|
Bar-Graph
|
%
of existing Current vs OC setting current
|
|
Mounting
|
35mm DIN-Rail
|
|
|
|
|
|
|
| |

EOCR-3M420
|